Electrical Ratings(3Phase) Symmetrical Basis | |
Rated Frequency | 50/60Hz |
Rated Maximum Line to Line Voltage | 7.2kV,r.m.s |
Rated Power Frequency Withstand Voltage:Air | 28kV,r.m.s |
Rated Impulse Withstand Voltage:Air | 60kV,Peak |
Rated Normal Current | 3150A |
Rated Short- Circuit Current ( 3 Phase Symmetrical Basis) | 60kA,r.m.s |
Percentage D.C. Component of Rated S.C. Breaking Current | |
Rated Short-Circuit Making Current | 130kA,Peak |
Rated Duration of Short Time Current | 4s |
Rated Short-Time Withstand Current | 60kA,r.m.s |
Rated Peak Withstand Current | 130kA,r.m.s |
*Maximum Contact Resistance at Minimum Closing Force | 18Micro ohms |
*Rated Breaking Current of Single Capacitor Bank | 630A,r.m.s |
*Rated Breaking Current of Back-to-Back Capacitor Bank | 400A,r.m.s |
Rated operating sequence | o-0.3s-co-180s-co |
Mechanical Data | |
Interrupter Weight(Approx.) | 6.46kg |
Moving Part Weight(Approx.) | 2.2kg |
Closing Force due to Bellow and Atmospheric | 120±50N |
Force Required to Hold Contacts open at Full Stroke | 190±60N |
Mechanical Requirements (Ref. Vcb) | |
Contact Stroke | 11±1 mm |
Opening Speed(average of 75 contact gap) | 1.2±0.2m/Sec |
Maximum Overtravel During Opening | 2mm |
Maximun Rebound During Opening | 2mm |
Closing Speed(average of last 30% contact gap) | 0.9±0.2m/Sec |
Maximum Contact Bounse Duration(with maximum 2 bounces) | â‰Â¤2ms |
Rated Contact Compressive Force | 4200±200N |
Closing and Opening non-simultaneity of three-phase Contacts | â‰Â¤2ms |
Life (Estimated) | |
Electrical Life at Rated Normal Current | 20,000 Operations |
Electrical Life at Rated Short Circuit Current | 100 Operations |
Mechanical Life | 20,000 Operations |
Contact Erosion Limit | 3mm |
Shelf Life | 20Years |